Brief description of the components Chapter 1) geothermal power plant: Component (SpCap 2) Heat pump system with closed circuit probes geothermal drilling veryicali. Voltage: 400 V/50 Hz Coolant: R 407 C Heat pump compressor capsule n.2-Scroll cooled with aspiration of freon, condenser of large size, mounted with built-stable, heat-insulating sheet rivestimemnto acoustic; condenser fitted with an expansion valve and glass inspection. Wiring harness including probes, and Safety HOW TO SET OUT IN THE FRAMEWORK OF FUNCTIONAL LOGIC PL. T.6 projects. PDC 1-2-3 (see PL. T.6) IDM TERRA Max 70 GA-P - R407c REVERSIBLE (Winter 35 ° C -- SUMMER 10 ° C) controlled by external PLC, including temperature sensors compatible wiring SPECIFICATIONS: -Power Rating: 76.8 kWt water 35/30 ° C - 5 ° C evaporator -Power consumption: 16.9 kw -COP (Coefficient of Performance): 4.55 Minimum side-flow evaporator: 11,300 l / h Evaporator-side pressure loss: 16 kPa Minimum Water Flow-side capacitor: 8200 l / h Loss of condenser-side pressure: 12 kPa -Dimensions: 1450x770x1190 (H) mm -Weight: 260 kg
STARTING CURRENT LIMITER: - For IDM TERRA MAX 70 MODULAR GAS HEAT GENERATOR, composed No.2 wall thermal modules condensing heating only: in aggregate pre-assembled with a single outer casing for operating room sealed CE approved and ISPESL. FERROLI - N.2 ECONCEPT 101 including form and equilibrated with approved safety ISPESL Ramp gas UNI. -Output power: 100 +100 = 200 kWt (50/30 ° C) Power-electr. ass.: 120 We - 1x220 V -Maximum operating pressure: 3 bar Capacity-expansion tank: 11 liters / cad. -Dia. external exhaust fumes: either 110 mm / cad. -Dia. outside air adduzzione: either 110 mm / cad. -Dim. Total: 1500 (L) x400 (w) x1650 (h) mm With: -unit set to operate under the management of external PLC variable speed pump heating PVC-pipe Øi 120 to 1 ml for replacement air boiler cupboard with Grid insects or anti-140 The pipe-white enamel 1.5 ml for boiler air intake, with grid anti-insects or 140 No.2-ventilation grills as TAV. T.2, useful section 0.3 square meters each. -mounting frame complete with expansion tank capacity 11 liters taps cover-kit taps kit condensate drain piped in PE DN 40 seconds UNI 11071 Smoke-splitter -electrical connection to the "point boiler" provided by the works electrical, but coordinated by hydraulic system that will provide schematic and assistance Form-balanced with adequate safety devices ISPESL Ramp-gas in accordance with fuel interception valve Ø 1 1 / 2 " -Safety valve Ø 3 / 4 "- 3 bar. Set Download SMOKE "FERROLI" PPS or steel, for operation boiler room sealed battery accessories to be verified in YARD, comprising: -curve at 90 ° -trims (inspection and various) collector tilted to horizontal flue boilers No.2 modules, or the second standards and requirements the manufacturer, with cladding kit exhaust fumes condensate terminal with unloading convoy. The exhaust fumes of the two units in battery run inside a air shaft for the exclusive use technical or otherwise provided with a plate of separation from other uses. Tank in galvanized steel with INTERNAL GLAZING FOR HOT WATER AND CHILLED Type HFL or ACV, with thermal insulation and condensation elastomer foam of 70 mm and finish SKY (Ref PL. T.6 - Tank "ACF") With: No.2-flanged Ø3 "side heat pumps; No.2-attacks Ø3 "side users; No.2-attacks Ø3 "center forces of 90 ° relative to the previous attacks; No.2-wells for temperature sensors and thermometer; n.1 drain tap; n.1 attack breather. Type: HFL - Mod VKT with conveyor internal flow - 1500 l with 6 attacks or equivalent ACV Size Ø 990 x (H) 2470 mm Tank in galvanized steel with INTERNAL GLAZING FOR HOT WATER AND CHILLED Type HFL or ACV, with thermal insulation and condensation elastomer foam of 70 mm and finish SKY (Ref PL. T.6 - Tanks "AT1" and "AT2") With: No.2-DN65 flanged side heat pumps; No.2-side attacks DN65 users; No.2 attacks DN25-user side (heat exchanger recirculation); Type: HFL - Mod VKT 4000 liters with 6 attacks or equivalent ACV Dim or 1440 x (H) 2855 mm Tank in galvanized steel with INTERNAL GLAZING FOR HOT WATER AND CHILLED Type HFL or ACV, with thermal insulation and condensation elastomer foam of 70 mm and finish SKY (Ref PL. T.6 - Tank "AT3") With: No.2 flanged DN100-side heat pumps; No.2-side attacks DN100 users; No.2 attacks DN100-center forces of 90 ° with respect to previous attacks; No.2-wells for temperature sensors and thermometer; n.1 drain tap; n.1 attack breather. Type: HFL - Mod VKT 4000 liters with 6 attacks or equivalent ACV Dim or 1440 x (H) 2855 mm 
Chapter 2) GEOTHERMAL FIELD PROBES (SpCap 3)
PROBES GEOTHERMAL DRILLING HDPE PN16 DN40, formed a "U" with special test probe, laying and filling bentonite. TECHNICAL DATA (see PL. SG.2-v2) n.40-probes of 100 m / cad. - Tot 4000 m; PE pipe DN40-PN16; pipe DN50-attack; POWER-EXCHANGE guaranteed supplier: 200 kWt. INCLUDED: test the thermal response to a probe sample; APAT-communication and practice in the Province (if required); -removal or spreading bentonite drilling second law. PROBE TOTAL N.40 - Depth '100 ml / each. TOTAL 4000 ml TO BE CONFIRMED AFTER THE FIRST TEST OF THE PROBE YIELD. MIXED GREEN IN BARRELS antifreeze glycol based Propylene, for circuit protection probes - Collectors - pumps heat, with a mixture of 20%. The mixture must be original "IDM-Suntek, under penalty of forfeiture of the guarantee of geothermal heat pumps ..
Ch.3) geothermal: THE NETWORK CONNECTION PROBES TO THE FIELDS IN CENTRAL HEAT COLLECTOR (SpCap 4) THERMOMETER BIMETALLIC with radial-mounted or rear of 0 100 in cash and cast polished chrome band, white dial, sheath for removable installation on pipes in the cockpit. scale -10 / +30 ° C FILTER COLLECTOR unclean 'BRONZE AY, with attacks threaded bronze body, to exercise up to 100 ° C - PN 6, installed upstream of the pumps. Element in perforated sheet of stainless steel AISI-304, thickness minimum of 0.5 mm. DN65 HIGH DENSITY POLYETHYLENE PIPES 'FOR LIQUID PRESSURE, non-toxic, suitable for use in the waterworks field, with max PN10. Supplied and installed complete with special pieces, bends, fittings (even with steel pipes) and any other accessories needed for implementing the network. Burden for coordination of the excavation of the trench laying of pipelines size of 40 cm wide by 100 cm in depth, bed pose (20 cm) and coverage (20 cm) with sand and tape reporting on entire route (OPERA as the undertaking construction). PIPING CONNECTION BETWEEN THE FIELDS AND PROBES COLLECTORS IN PE DN180 POSTS IN CENTRAL HEAT. PE 100 PN 10 - DN 40 - ml 450 PE 100 PN 10 - DN 50 - ml 270 PE 100 PN 10 - DN 63 - ML 75 PE 100 PN 10 - DN 75 - ml 495 | CONNECTION BETWEEN THE PIPES MANIFOLDS IN PE DN180 POSTS IN CENTRAL HEAT AND OF EVAPORATORS FOUR HEAT PUMPS. STAINLESS STEEL TO PRESS, Type Mapress / Geberit: Ø 2 1 / 2 " Ø 4 " PIPING CONNECTION BETWEEN THE FIELDS AND PROBES COLLECTORS IN PE DN180 POSTS IN CENTRAL HEAT. PE 100 PN 10 - DN 40 - ml 450 PE 100 PN 10 - DN 50 - ml 270 PE 100 PN 10 - DN 63 - ML 75 PE 100 PN 10 - DN 75 - ml 495 CONNECTION BETWEEN THE PIPES MANIFOLDS IN PE DN180 POSTS IN CENTRAL HEAT AND OF EVAPORATORS FOUR HEAT PUMPS. STAINLESS STEEL TO PRESS, Type Mapress / Geberit: Ø 2 1 / 2 " Ø 4 " COLLECTORS PE 100 PN 10 - DN 180 for connecting pumping borehole heat exchangers and evaporators, pumping heat pumps. No.6 + n.6 attacks - DN 65 Valves with control lever, ring estate NBR. Circuit connected to collectors in thermal power stations. PN 10 - DN 65 VALVE CALIBRATION - PN 10 - DN 100 CHECK VALVE DISC with flanged, including accessories. DN65 FLANGED Rubber Expansion Joints, Rubber Body chloroprene reinforced with fabric inserts, dinghies steel connecting, detachable swivel flanges and carbon steel UNI 2278 PN 16, including flanges, bolts, gaskets. DN65 GAUGE FOR CHECKING RADIAL ISPESL approved, with threaded brass coupling, brass faucet portamanometro sandblasted, with power pressure flange standard 40 mm x 4 mm thickness. Attacks male-female, shaft sealing and Lela stuffing box. Plated copper tube coil 8 mm., Male fixed - female swivel for instrument protection. scale of work: 0-5 bar SAFETY VALVE SPRING APPROVED FOR HEATING with overpressure of 10% to 20% gap closure, threaded. Body, cap, plate and rod in brass, diaphragm and seals EPDM seal resistant up to 140 ° C, steel spring special NiCr, imbuoto exhaust discharge piped to the nearest point. Type CALEFFI - Mod 5274 + funnel 5521 Ø 1 / 2 "- 3 bar THERMAL AND ANTI PIPES, realized with styrofoam cups. POLYSTYRENE mold thickness 20 mm and cladding tube PVC flexible corrugated sealed: - DN 40 - ml 450 - DN 50 - ml 270 - DN 63 - ML 75 - DN 75 - ml 495 - DN 180 with finishing Isogenopack - 5 ml
INSULATION SLEEVING HOSE STAINLESS STEEL TYPE MEPRESS ARMAFLEX AF 16 mm thick PVC-finish ISOGENOPACK: Ø 2 1 / 2 "- 75 ml Ø 4 - 30 ml TANK EP for collecting waste liquid circuit probes, capacity 50 liters. Drain cock Ø 3 / 4 ".

CAP.4) geothermal power plant: NETWORK DISTRIBUTION COMPONENTS AND PUMPING (SpCap 5) Closed expansion tank diaphragm steel with cushion Nitrogen membrane neoprene clip for temperature up to 100 ° C. Precharge pressure: 1.5 bar (Ref PL. T.6). CIRCUIT PROBES GEOTHERMAL: capacity 35 liters / 1.5 bar HOT-COLD STORAGE TANK "ACF": capacity 150 liters / 1.5 bar TANK "AT1" and "AT2" capacity 80 liters / 1.5 bar TANK "AT3": capacity 35 liters / 1.5 bar SAFETY VALVE SPRING APPROVED FOR HEATING with overpressure of 10% to 20% gap closure, threaded. Body, cap, plate and rod in brass, diaphragm and seals EPDM seal resistant up to 140'C, special steel spring NiCr, imbuoto exhaust discharge piped to the nearest point. Type CALEFFI - Mod 5274 + funnel 5521 - Ø 1 / 2 "- 3 bar GAUGE FOR CHECKING RADIAL ISPESL approved, with threaded brass coupling, brass faucet portamanometro sandblasted, with power pressure flange standard 40 mm x 4 mm thickness. Attacks male-female, shaft sealing and Lela stuffing box. Plated copper tube coil 8 mm., Male fixed - female swivel for instrument protection. scale of work: 0-5 bar
THERMOMETER BIMETALLIC with radial-mounted or rear of 0 100 in cash and cast polished chrome band, white dial, sheath for removable installation on pipes in the cockpit. scale 0-30 ° C scale 0-50 ° C scale 10-100 ° C scale 10-150 ° C Drain cocks attack with chemical cleaning heat exchangers.
AUTO GROUP OF WATER SUPPLY, comprising: automatic feeder with gauge-type CALEFFI mod. 554,150 Ø3 / 4 " No. 3-ball valves with by-pass for quick charge Ø3 / 4. Disarò - DEFANGATORE "CALEFFI" STEEL, capable function in temperatures up to 100 ° C and pressure PN10, complete Automatic air vent valve, drain cock impurities. With: -shell insulation -flanges, bolts and gaskets (all insulated). Type CALEFFI DISCAL - Mod 546,060 - DN65 Disarò "CALEFFI" STEEL, capable of running on temperatures up to 100 ° C and pressure PN10, complete with valve automatic air vent, drain tap impurities. With: -shell insulation -flanges, bolts and gaskets (all insulated). Type CALEFFI DISCAL - Mod 551103rd - DN100
VALVE Automatic air vent for floating body bronze with threaded, complete with tap exclusion spring stainless steel. Type CALEFFI - Mod DISCAL 551,004 - Ø 1 / 2 "with faucet exclusion. SINGLE ELECTRIC FOR DIRECT MOUNTING ON Pipes with threaded or flanged. WILO WITH FORMS IF / PLR FOR COMMUNICATION WITH SYSTEM Supervision. Cast iron impeller in stainless steel, motor immersed directly coupled to the impeller, suitable for heating and air conditioning. Supplied and installed complete with fittings, flanges, gaskets and support staff. P1 - P2 - P3: COLLECTOR CIRCUIT PROBES - EVAPORATORS PDC1-2-3 WILO - Mod Verolini IP-E 65/115 - 1,5 / 2 - 3x380 V - 1.5 kWe Form No. 1 with IF P4 - P5 - P6: CHIP CAPACITOR - TANK "ACF" WILO - Mod Verolini IP-E 50/115 - 0,75 / 2 - 3x380 V - 750 W Form No. 1 with IF P7: |