Installations designed in accordance with standard ISO 14644.
Results obtained
Summer temperature 20 ° C ± 1 ° C Winter temperature 20 ° C ± 1 ° C Humidity 50% ± 5% Data underlying the project Room 5A ISO 8 Room 5B ISO 8
Room 5C ISO 8
Room 5D ISO 8
Room 5E ISO 8
Room 5F ISO 7
Room 5G ISO 7
Room 5H ISO 8
Room 5I ISO 8
Double 5L ISO 8
Parts guaranteed minimum outside air according to ISO 14644-2-2001 (E) with the room height 3.0 meters ISO 7 = 10 to 20 m3 / h m2 ISO 8 = 30 to 70 m3 / h m2
Room 5A 1,500 m3 / 126 m2 = 11.9 m3 / h m2 * Room 5B 50 m3 / 4 m2 = 12.5 m3 / h m2 *
Room 5C 70 m3 / 6 m2 = 11.6 m3 / h m2 *
Room 5D 60 m3 / 5.2 m2 = 11.5 m3 / h m2 *
Room 5E 60 m3 / 5.2 m2 = 11.5 m3 / h m2 *
5F Room 100 m3 / 3 m2 = 33.3 m3 / h m2 *
Room 5G 5,000 m3 / 153 m2 = 32.6 m3 / h m2 *
Room 5H 1,100 m3 / 96 m2 = 11.4 m3 / h m2 *
Room 5I 40 m3 / 3 m2 = 13.3 m3 / h m2 *
Double 5L 1,200 m3 / 108 m2 = 11.1 m3 / h m2 * |