Data underlying the project: Net dimensions of the treated 4.5 mt. x 3 mt. h 3 mt. Load thermal equipment constant Structures Laboratory Isolate Admission to the laboratory with compass glass separation from other departments Doubles Achievements: Minimum summer temperature refrigeration system with 20 ° C High winter heating temperature 20 ° C Maximum humidity reached 65% with humidifier Airflow total 1580 m3 / h Consumption conditioning system: Electrical power consumption 5.7 Kw. Water Consumption 0.002 m3 / h |  |
CLOSET CONDITIONS - Structure painted panels.
- Socket base.
- Filter cells.
- Refrigerant gas compressor.
- Direct expansion cooling coil.
- Heating coil.
- Immersed electrode humidifiers.
- Centrifugal fan with variable speed delivery.
- Control unit and microprocessor control.
|  |
PIPING CONNECTION - For the connection between the conditioner and the condenser (up to 10 meters away).
|  |
| REMOTE AIR COOLED CONDENSER |  |
Duct - Panels of polyurethane foam self-supporting film-coated aluminum.
- Circular diffuser fins complete the calibration.
|  |
DOUBLE INSULATED - Panels pre-painted and insulated with polyurethane foam injected between the two sheets.
- Profiles of pre-painted finish.
- Floor with rubber cover.
- Double glazing with air chamber.
- Dimensions as dis. C5202DP1 attachment.
|  |
Inspection door - Made with galvanized sheet metal and plastic, insulated with polyurethane foam injected between the two sheets.
|  |